- BrandArtikul Azia Kabel
- Country of manufactureUzbekistan
Power cables NYM
NYM - the power cable with a copper conducting vein, with isolation and a cover from polyvinylchloride plastic compound, with filling of space between veins
Scope
The cable is intended for transfer and distribution of electric energy in stationary installations on an alternating voltage to 0,66 kV with a frequency of 50 Hz, including in electroinstallations of buildings and constructions for safe use of electric equipment of a class of protection 1 on electrical safety.
Application of a cable over and in plaster, in dry, damp and wet rooms, and also in a bricklaying and concrete is possible. Laying can be carried out in pipes, in the closed adjusting and curved channels. Besides, laying of a cable on a tree is allowed
Design
Wire brand | Description |
NYM | Vein - the single-wire or multiwire copper conductor Isolation - polyvinylchloride plastic compound with distinctive coloring according to the European DIN VDE 0250 standard: Internal cover - termoelastoplast Cover - polyvinylchloride plastic compound or polyvinylchloride plastic compound of the lowered combustibility |
Coloring of conducting veins
black and blue | The 3rd vein greenish-yellow, black and blue |
The 4th vein greenish-yellow, brown, black and blue sections |
The 5th vein greenish-yellow, black, blue, brown, sections |
Technical characteristics
Name of characteristics | Value of characteristics |
Working tension, kV | 0,66 |
Number of veins | from 1 to 5 |
Section of the main veins, mm ² | from 1,5 to 50 |
Section of zero veins, mm ² | from 1,5 to 25 |
Class of conducting veins | 1 or 2 |
Construction length, m | not less than 100 |
Temperature of operation, °C common industrial execution executions "нг" - the lowered combustibility |
from-50 to +50 from-30 to +50 |
Resistance of isolation, megohm, not less for the section of 1,5 mm ² for sections from 2,5 to 6,0 mm ² for the sections of 10 mm ² above |
10 9 7 |
The minimum radius of a bend when laying, diameters of a cable | 20 |
Execution regarding fire safety not extending burning at single laying not extending burning at group laying (ng): on the category A F/R on category ng (And) on category ng (In) |
(without designation)
ng (And F/R) |
Cable service life | not less than 15 years |